The AEMC 8333 three-phase power quality analyzer is capable of storing up to 12 screen snapshots, 51 transient captures (each four cycles long), and 4,000 alarm events across up to 10 parameters. It records trend data over days, weeks, or months and features IEC 61000-4-30 Class B compliance with safety ratings of 600 V CAT IV. The device includes three current and four voltage input terminals. It provides true RMS measurements for single-, two-, and three-phase systems at 256 samples per cycle, with real-time color waveforms, automated probe recognition, and scaling. Capable of measuring DC volts, amps, and power, it displays and captures harmonics up to the 50th order, including directional data. The analyzer detects transients down to 1/256th of a cycle and stores extensive logged data. Additional features include phasor diagrams, per-phase and total real power (W), apparent power (VA), reactive power (VAR), energy consumption (kWh, VARh, kVAh), neutral current calculations, transformer K-factor, power factor, and flicker analysis. It displays phase unbalance, harmonic distortion, alarms, surges, sags, and captures waveforms via screen snapshot. The included DataView® software facilitates data configuration, real-time display, analysis, and reporting. Ideal for electrical monitoring, harmonic analysis, utility testing, energy management, power factor correction, industrial and commercial electrical troubleshooting.