The CARLING TECHNOLOGIES B-Series circuit breaker is designed for world market applications, utilizing hydraulic magnetic principles for precise operation even in extreme temperatures. Typical applications include power supplies, medical equipment, office equipment, control panels, and marine equipment. It meets CSA Standard 22.2 No. 100 and offers a range of configurations including 1-6 poles, current ratings from 0.02 to 50 amps, and various voltage options. The B-Series is UL Listed, CSA Accepted, TUV Certified, and VDE Certified, ensuring reliable protection across a wide range of industrial and commercial applications. It is built to withstand shock, vibration, moisture, and thermal shock, making it suitable for demanding environments.
insulation_resistance: Minimum of 100 Megohms at 500 VDC
dielectric_strength: UL, CSA - 1500 V 50/60 Hz for one minute
trip_free: All B-Series Circuit Breakers will trip on overload
trip_indication: The operating Handle moves positively to the OFF position when an overload causes the breaker to trip.
number_of_poles: 1 - 6 poles at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps.
internal_circuit_config: Series, (with or without auxiliary switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without auxiliary switch)
weight: Approximately 65 grams/pole
standard_colors: Housing- Black; Actuator - See Ordering Scheme
operating_temperature: -40° C to +85° C
shock_resistance: Withstands 100 Gs, 6ms
vibration_resistance: Withstands 0.060" excursion from 10-55 Hz
moisture_resistance: Ten 24-hour cycles @ + 25°C to +65°C, 80-98% RH