Carling Technologies CA1B224610121C C-Series Circuit Breaker

Carling Technologies' C-Series hydraulic-magnetic circuit breakers provide a robust solution for applications demanding high amperage and voltage capabilities within a smaller footprint. Featuring a unique arc chute design, these breakers boast increased interrupting capacities up to 10,000 amps. Constructed with a new thermoset glass-filled polyester half shell, the C-Series offers enhanced mechanical and electrical strength. Available with American Standard or Metric threaded stud terminals, or saddle clamp screw terminals, and an optional mid-trip handle style actuator for visual overload indication, these circuit breakers are suitable for marine, telecom/datacom, military, renewable energy, and generator/welder applications.

Authorized Distributors
Source:DigiKey
Part No:CA1-B2-24-610-121-C
Stock:0
Inv Date:06-06-2026
Price: Unit price: $40.617
Buy/RFQ:
Source:DigiKey
Part No:CA1B224610121C
Stock:0
Inv Date:06-06-2026
Price: Unit price: $40.617
Buy/RFQ:
Part No:CA1-B2-24-610-121-C
Stock:0
Inv Date:06-07-2026
Price: Unit price: $67.24
Buy/RFQ:
Part No:CA1-B2-24-610-121-C
Stock:2
Inv Date:06-06-2026
Price: Unit price: $66.48
Buy/RFQ:
Part No:CA1-B2-24-610-121-C
Stock:0
Inv Date:06-06-2026
Price: Unit price: $75.06
Buy/RFQ:
Part No:CA1-B2-24-610-121-C
Stock:0
Inv Date:06-06-2026
Price: Unit price: $75.06
Buy/RFQ:

Carling Technologies CA1B224610121C C-Series Circuit Breaker Specifications:

  • Physical: Approx.112 grams/pole ( 3.95 oz)
  • Environmental: Withstands 100 Gs, 6ms sawtooth while carrying rated current; Withstands 0.060” excursion from 10-55 Hz & 10 Gs 55-500 Hz; Method 106D, i.e., ten 24-hour cycles @ +25°C to +65°C, 80-98% RH; Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs); Method 107D, Condition A (five cycles @ -55°C to +25°C to +85°C to +25°C)
  • Maximum Voltage: AC, 480 WYE/277 VAC, 50/60 Hz (see Table A.); UL489: AC,240 VAC. (See Table D), 50/60 Hz, 125 VDC
  • Current Rating: Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 25.0, 30.0, 35.0, 40.0, 50.0, 60.0, 70.0, 80.0, 90.0 and 100 amps. Other ratings available
  • Standard Voltage Coils: DC - 6V, 12V; AC - 120V
  • Auxiliary Switch Rating: SPDT; 10.1 amps-250VAC, DC Aux. Switch 1.0A, 65 VDC. 0.5A, 80VDC,1/4 HP, 125VAC,VDE & TUV 1.0 125 VAC
  • Insulation Resistance: Minimum of 100 Megohms at 500 VDC
  • Dielectric Strength: UL, CSA: 1960 V 50/60 Hz for one minute between all electrically isolated terminals
  • Endurance: 10,000 ON-OFF operations @ 6 per minute; with rated current & voltage
  • Trip Free: All C-Series circuit breakers will trip on overload, even when actuator is forcibly held in the ON position
  • Number of Poles: 1-6 poles ≤ 50A; 1-4 poles @ 51-70A; 1-2 poles 71-100A
  • Internal Circuit Configuration: Series (with or without auxiliary switch, mid trip & mid trip with alarm switch) Shunt & Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without aux. switch)

Buy the CA1-B2-24-610-121-C CARLING TECHNOLOGIES C-Series Circuit Breaker | myMectronic

Purchase the Carling Technologies CA1-B2-24-610-121-C C-Series Circuit Breaker securely and efficiently online.

Buy Now

Frequently Asked Questions

Where can I buy Carling Technologies CA1B224610121C?

You can click on the BUY or RFQ button to purchase CA1B224610121C from an authorized Carling Technologies distributor.

How do I troubleshoot issues or seek technical support for part CA1B224610121C?

You can download the CA1B224610121C datasheet or visit the Carling Technologies website for support.

Who is the manufacturer of CA1B224610121C?

Carling Technologies

Carling Technologies Part List

Browse and search other Carling Technologies parts, locate datasheets and stock

Sponsored by