SIEMENS ENERGY 3RV10111DA10 Motor Protection Circuit Breaker

The Siemens 3RV1011-1DA10 is a compact and versatile motor protection circuit breaker suitable for a wide range of industrial applications. This S00 sized breaker offers adjustable overload protection with a pickup current range of 2.2 to 3.2 Amps and a release current of 42 Amps. It is designed to protect three-phase AC motors and features a screw-type terminal connection for easy installation. The breaker's robust design and reliable performance make it ideal for use in machinery, pumps, fans, and other motor-driven equipment. It also includes phase failure detection for enhanced protection.

Authorized Distributors
Source:DigiKey
Part No:3RV10111DA10
Stock:1
Inv Date:05-29-2026
Price: Unit price: $410.7
Buy/RFQ:
Part No:3RV10111DA10
Stock:3
Inv Date:05-30-2026
Price: Unit price: $404.11
Buy/RFQ:
Part No:3RV1011-1DA10
Stock:0
Inv Date:05-30-2026
Price: N/A
Buy/RFQ:
Part No:3RV1011-1DA10
Stock:7
Inv Date:05-29-2026
Price: Unit price: $429.65
Buy/RFQ:
Part No:3RV1011-1DA10
Stock:4
Inv Date:05-29-2026
Price: Unit price: $424.35
Buy/RFQ:
Part No:3RV1011-1DA10
Stock:4
Inv Date:05-29-2026
Price: Unit price: $424.35
Buy/RFQ:

SIEMENS ENERGY 3RV10111DA10 Motor Protection Circuit Breaker Specifications:

  • Product brand name: SIRIUS
  • Product designation: Circuit breaker
  • Design of the product: For motor protection
  • Product type designation: 3RV1
  • Size of the circuit-breaker: S00
  • Size of contactor can be combined: S00
  • Auxiliary switch: Yes
  • Power loss at AC (hot operating state): 7.25 W
  • Power loss per pole at AC (hot operating state): 2.4 W
  • Insulation voltage: 690 V
  • Surge voltage resistance: 6 kV
  • Maximum permissible voltage for safe isolation: 400 V
  • IP rating (front): IP20
  • IP rating (terminal): IP00
  • Mechanical service life: 100,000 cycles
  • Electrical endurance: 100,000 cycles
  • ATEX directive type: Ex II (2) GD
  • ATEX certificate: DMT 02 ATEX F 001
  • DIN EN 81346-2 reference code: Q
  • Maximum installation altitude: 2,000 m
  • Operating ambient temperature: -20 ... +60 °C
  • Storage ambient temperature: -50 ... +80 °C
  • Transport ambient temperature: -50 ... +80 °C
  • Temperature compensation: -20 ... +60 °C
  • Relative humidity during operation: 10 ... 95 %
  • Number of poles for main circuit: 3
  • Adjustable pick-up value current: 2.2 ... 3.2 A
  • Operating voltage (rated value): 690 V
  • Operating voltage (AC-3 rated value max): 690 V
  • Operating frequency (rated value): 50 ... 60 Hz
  • Operating current (rated value): 3.2 A
  • Operating current (at AC-3, 400 V): 3.2 A
  • Operating power (at AC-3, 230 V): 550 W
  • Operating power (at AC-3, 400 V): 1,100 W
  • Operating power (at AC-3, 500 V): 1,500 W
  • Operating power (at AC-3, 690 V): 2,200 W
  • Maximum operating frequency: 15 1/h
  • Number of auxiliary contacts: 0
  • Ground fault detection: No
  • Phase failure detection: Yes
  • Trip class: CLASS 10
  • Overload release design: thermal
  • Short-circuit current breaking capacity (Ics) at AC (240 V): 100,000 A
  • Short-circuit current breaking capacity (Ics) at AC (400 V): 100,000 A
  • Short-circuit current breaking capacity (Ics) at AC (500 V): 3,000 A
  • Short-circuit current breaking capacity (Ics) at AC (690 V): 2,000 A
  • Maximum short-circuit current breaking capacity (Icu) at AC (240 V): 100 kA
  • Maximum short-circuit current breaking capacity (Icu) at AC (400 V): 100 kA
  • Maximum short-circuit current breaking capacity (Icu) at AC (500 V): 3 kA
  • Maximum short-circuit current breaking capacity (Icu) at AC (690 V): 2 kA
  • Instantaneous short-circuit trip unit: 42 A
  • Full-load current (FLA) at 480 V: 3.2 A
  • Full-load current (FLA) at 600 V: 3.2 A
  • Mechanical performance (hp) at 110/120 V: 0.1 hp
  • Mechanical performance (hp) at 230 V: 0.25 hp
  • Mechanical performance (hp) at 200/208 V: 0.5 hp
  • Mechanical performance (hp) at 220/230 V: 0.75 hp
  • Mechanical performance (hp) at 460/480 V: 1.5 hp
  • Mechanical performance (hp) at 575/600 V: 2 hp
  • Mounting position: any
  • Mounting type: screw and snap-on mounting
  • Height: 90 mm
  • Width: 45 mm
  • Depth: 75 mm
  • Removable terminal for auxiliary circuit: No
  • Electrical connection (main circuit): screw-type terminals
  • Electrical connector arrangement (main circuit): Top and bottom
  • Connectable conductor cross-sections (main contacts): 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x (1 ... 4 mm²)
  • Connectable conductor cross-sections (auxiliary contacts): 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
  • Tightening torque (main contacts): 0.8 ... 1.2 N·m
  • Tightening torque (auxiliary contacts): 0.8 ... 1.2 N·m
  • Screwdriver tip size: Pozidriv 2
  • Connection screw thread: M3
  • B10 value (high demand rate): 5,000
  • Dangerous failure proportion (low demand rate): 50 %
  • Dangerous failure proportion (high demand rate): 50 %
  • Failure rate (FIT) (low demand rate): 50 FIT

Buy the 3RV1011-1DA10 SIEMENS ENERGY Motor Protection Circuit Breaker | myMectronic

Purchase the Siemens 3RV1011-1DA10 Motor Protection Circuit Breaker securely and conveniently online.

Buy Now

Frequently Asked Questions

Where can I buy SIEMENS ENERGY 3RV10111DA10?

You can click on the BUY or RFQ button to purchase 3RV10111DA10 from an authorized SIEMENS ENERGY distributor.

How do I troubleshoot issues or seek technical support for part 3RV10111DA10?

You can download the 3RV10111DA10 datasheet or visit the SIEMENS ENERGY website for support.

Who is the manufacturer of 3RV10111DA10?

SIEMENS ENERGY

SIEMENS ENERGY Part List

Browse and search other SIEMENS ENERGY parts, locate datasheets and stock

Sponsored by