The CARLING TECHNOLOGIES B-Series circuit breaker is designed for world market applications, employing hydraulic magnetic principles to ensure precise and reliable operation even in extreme temperatures. Typical applications include power supplies, medical equipment, office equipment, control panels, and marine equipment. The series meets CSA Standard 22.2 No. 100 for Generator & Welder markets and offers a wide range of configurations including poles, current ratings, and actuator colors. It is UL Recognized and CSA Accepted, providing robust protection for various electrical systems.
Insulation Resistance: Minimum of 100 Megohms at 500 VDC
Dielectric Strength: UL, CSA - 1500 V 50/60 Hz for one minute
Number of Poles: 1 - 6 poles at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps.
Internal Circuit Config: Series, (with or without auxiliary switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without auxiliary switch)
Weight: Approximately 65 grams/pole
Standard Colors: Housing- Black; Actuator - See Ordering Scheme
Operating Temperature: -40° C to +85° C
Shock Withstands: 100 Gs, 6ms
Vibration Withstands: 0.060" excursion from 10-55 Hz
Moisture Resistance: Method 106D
Thermal Shock: Method 107D