myMectronic
myMectronic

A Premier B2B Part Search

Carling Technologies PBABA246202BAAG PB-Series Circuit Breaker

The CARLING TECHNOLOGIES PB-Series circuit breaker is a versatile device designed to provide comprehensive protection in a single package. Utilizing the hydraulic magnetic principle, it offers precise operation and performance even in challenging environments with extreme temperatures. This RCBO (Residual Current Circuit Breaker with Overcurrent Protection) integrates ground fault protection with the familiar overcurrent tripping characteristics of a standard circuit breaker. Its temperature stability eliminates the need for derating and minimizes nuisance tripping. The PB-Series is ideal for applications such as boats, marinas, and areas near water, where electrical shock hazards are a concern. It detects lower-level ground faults that ordinary circuit breakers may miss, reducing the risk of fires and electrical shock. The breaker's features include overload, short circuit, and ground fault protection, handle or rocker style actuators, and a trip-free mechanism for enhanced safety.

Authorized Distributors
Part No:PBA-BA-24-620-2BA-AG
Stock:0
Inv Date:06-07-2026
Price: N/A
Buy/RFQ:
Part No:PBA-BA-24-620-2BA-AG
Stock:2
Inv Date:06-06-2026
Price: Unit price: $110
Buy/RFQ:
Part No:PBA-BA-24-620-2BA-AG
Stock:2
Inv Date:06-06-2026
Price: Unit price: $110
Buy/RFQ:

Carling Technologies PBABA246202BAAG PB-Series Circuit Breaker Specifications:

  • Maximum Voltage: 120/240VAC 60 Hz
  • Current Ratings: Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0 & 30.0 amps
  • Insulation Resistance: Minimum of 100 Megohms at 500 VDC
  • Dielectric Strength: UL, CUL - 1500 V 60 Hz for one minute between all electrically isolated terminals
  • Impedance Values: From Line to Load Terminal
  • Leakage To Ground: Standard: Must Trip 120/240VAC 60 Hz Leakage Current Ratings 5 & 30 milliamps
  • Trip Time: 300 ms Max. @ 100%, 40ms Max. @ 500% of must trip leakage current
  • Endurance: 10,000 ON-OFF operations @ 6 per minute
  • Trip Free: All PB-Series Circuit Breakers will trip on overload or ground fault, even when Handle is forcibly held in the ON position
  • Trip Indication: The operating Handle moves positively to the OFF position when an overload or ground fault causes the breaker to trip
  • Number of Poles: 1 - 3 poles
  • Internal Circuit Config: Series Trip
  • Weight: Approximately 65 grams/pole
  • Operating Temperature: -35° C to +65° C
  • Shock: Withstands 100 Gs, 6ms, sawtooth while carrying rated current
  • Vibration: Withstands 0.060” excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current
  • Moisture Resistance: Method 106D, i.e., ten 24-hour cycles @ + 25°C to +65°C, 80-98% RH
  • Thermal Shock: Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C)
  • Corrosion: Tested per UL943 FMG Test. 3 weeks @ 30°C 75% RH, 100ppb H2S, 20ppb CI2, 200ppb NO2
  • Agency Certifications: UL Listed, UL Standard 489, UL Standard 1077, UL Standard 943, UL Standard 1053

Buy the PBA-BA-24-620-2BA-AG CARLING TECHNOLOGIES PB-Series Circuit Breaker | myMectronic

Purchase the CARLING TECHNOLOGIES PBA-BA-24-620-2BA-AG PB-Series Circuit Breaker securely and conveniently online.

Buy Now

Frequently Asked Questions

Where can I buy Carling Technologies PBABA246202BAAG?

You can click on the BUY or RFQ button to purchase PBABA246202BAAG from an authorized Carling Technologies distributor.

How do I troubleshoot issues or seek technical support for part PBABA246202BAAG?

You can download the PBABA246202BAAG datasheet or visit the Carling Technologies website for support.

Who is the manufacturer of PBABA246202BAAG?

Carling Technologies

Carling Technologies Part List

Browse and search other Carling Technologies parts, locate datasheets and stock

Sponsored by