myMectronic
myMectronic

A Premier B2B Part Search

Phoenix Contact 2865984 2-Channel Isolation Amplifier

The Phoenix Contact MACX MCR-EX-SL-2NAM-R-UP is a robust and versatile 2-channel isolation amplifier specifically engineered for use in demanding industrial environments, particularly those classified as hazardous. This amplifier provides galvanic isolation between the input and output circuits, protecting sensitive equipment from voltage spikes and noise. It incorporates a wide-range power supply, accommodating various voltage levels, and features a relay output with a PDT contact for signal transmission. The integrated line fault detection (LFD) enhances safety by indicating potential issues through a visual LED signal. Its compliance with standards like EN 61508 and its suitability for installation in zone 2 make it ideal for applications in the process industries, oil and gas, and other sectors requiring reliable and safe signal conditioning.

Authorized Distributors
Source:DigiKey
Part No:2865984
Stock:40
Inv Date:05-28-2026
Price: Unit price: $323.23
Buy/RFQ:
Part No:2865984
Stock:31
Inv Date:05-29-2026
Price: Unit price: $336.15
Buy/RFQ:
Part No:2865984
Stock:0
Inv Date:05-28-2026
Price: Unit price: $355.34
Buy/RFQ:
Part No:2865984
Stock:13
Inv Date:05-28-2026
Price: Unit price: $340.24
Buy/RFQ:
Part No:2865984
Stock:13
Inv Date:05-28-2026
Price: Unit price: $340.24
Buy/RFQ:

Phoenix Contact 2865984 2-Channel Isolation Amplifier Specifications:

  • Packing unit: 1 pc
  • Weight per Piece (excluding packing): 180.0 g
  • Custom tariff number: 85437090
  • Country of origin: Germany
  • Width: 17.5 mm
  • Height: 99 mm
  • Depth: 114.5 mm
  • Ambient temperature (operation): -20 °C ... 60 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Maximum altitude: ≤ 2000 m
  • Permissible humidity (operation): 10 % ... 95 % (non-condensing)
  • Noise immunity: EN 61000-6-2
  • Degree of protection: IP20
  • Non-load voltage: ~ 8 V DC
  • Switching points (attenuated): < 1.2 mA (blocking)
  • Switching points (unattenuated): > 2.1 mA (conductive)
  • Switching output: Relay output
  • Contact type: 1 PDT per channel
  • Contact material: AgSnO2, hard gold-plated
  • Maximum switching voltage (AC): 250 V AC (2 A, 60 Hz)
  • Maximum switching voltage (DC): 120 V DC (0.2 A)
  • Maximum switching voltage (DC2): 30 V DC (2 A)
  • Maximum switching capacity: 500 VA
  • Mechanical service life: 10 7 cycles
  • Supply voltage range: 24 V ... 230 V AC/DC (-20 % ... +10 %, 50 Hz ... 60 Hz)
  • Max. current consumption: < 80 mA
  • Power consumption: ≤ 1.3 W
  • Conductor cross section solid min.: 0.2 mm²
  • Conductor cross section solid max.: 2.5 mm²
  • Conductor cross section flexible min.: 0.2 mm²
  • Conductor cross section flexible max.: 2.5 mm²
  • Conductor cross section AWG min.: 24
  • Conductor cross section AWG max.: 14
  • Stripping length: 7 mm
  • Connection method: Screw connection
  • Tightening torque, min: 0.5 Nm
  • Tightening torque max: 0.6 Nm
  • No. of channels: 2
  • Step response (10-90%): typ. 6 ms (N/O contact: OFF/ON)
  • Step response (ON/OFF): typ. 6 ms (N/O contact: ON/OFF)
  • Step response (ON/OFF)2: typ. 4 ms (N/C contact: ON/OFF)
  • Step response (OFF/ON)2: typ. 10 ms (N/C contact: OFF/ON)
  • Status display: Green LED (supply voltage, PWR), LED yellow (switching state), Red LED (line errors)
  • Flammability rating according to UL 94: V0
  • Degree of pollution: 2
  • Overvoltage category: III
  • Housing material: PA 66-FR
  • Color: green
  • Electrical isolation (Input/Power Supply): 375 V (Peak value in accordance with EN 60079-11)
  • Electrical isolation (Output 1/Output 2/Input, Power Supply): 300 Vrms (Rated insulation voltage (overvoltage category III; degree of pollution 2, safe isolation as per EN 61010-1))
  • Test voltage: 2.5 kV AC (50 Hz, 1 min.)
  • Conformance: CE-compliant, additionally EN 61326
  • ATEX: II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, II 3(1) G Ex nA nC [ia Ga] IIC T4 Gc X
  • IECEx: [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex nA nC [ia Ga] IIC T4 Gc
  • UL, USA / Canada: Class I Div 2; IS for Class I, II, III Div 1
  • SIL: SIL 2
  • Max. output voltage Uo: 9.56 V
  • Max. output current Io: 10.3 mA
  • Max. output power Po: 25 mW
  • Group: IIC
  • Max. external inductivity Lo: 300 mH
  • Max. external capacity Co: 3.6 µF
  • Group2: IIB/IIIC
  • Max. external inductivity Lo2: 1000 mH
  • Max. external capacity Co2: 26 µF
  • Safety-related maximum voltage Um: 253 V AC/DC (Supply terminals)
  • Electromagnetic RF field: EN 61000-4-3
  • Fast transients (burst): EN 61000-4-4
  • Conducted interferences: EN 61000-4-6

Buy the 2865984 PHOENIX CONTACT 2-Channel Isolation Amplifier | myMectronic

Purchase the Phoenix Contact MACX MCR-EX-SL-2NAM-R-UP securely and efficiently for your industrial automation needs.

Buy Now

Frequently Asked Questions

Where can I buy Phoenix Contact 2865984?

You can click on the BUY or RFQ button to purchase 2865984 from an authorized Phoenix Contact distributor.

How do I troubleshoot issues or seek technical support for part 2865984?

You can download the 2865984 datasheet or visit the Phoenix Contact website for support.

Who is the manufacturer of 2865984?

Phoenix Contact